Specifications
Type of Environment and/or Equipment Interval Between Inspection and Tests
Class of Equipment Residual Current Devices (RCDs) Cord sets and power boards
Class l (protective l y earthed) Class ll (double insulated) Push-button test – by user Operating time and push-button test
Portable Fixed Portable Fixed
1. Factories, workshops, places of work or repair, manufacturing, assembly, maintenance or fabrication 6 months 12 months Daily or before every use 6 months 12 months 12 months 6 months
2. Environment where the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment 12 months 12 months 3 months 6 months 12 months 12 months 12 months
3. Environment where the equipment or supply cord is NOT subject to flexing in normal use and is NOT open to abuse and is NOT in hostile environment 5 years 5 years 3 months 6 months 2 years 2 years 5 years
4. Residential type areas of: hotels, residential institutions, motels, boarding houses, halls, hostels, accommodation houses and the like 2 years 2 years 6 months 6 months 2 years 2 years 2 years
5. Equipment for commercial cleaning  6 months 12 months 3 months N/A 12 months N/A 12 months
6. Hire equipment: Inspection Prior to hire Included push-button test by hirer, prior to hire N/A N/A Prior to hire
Hire equipment: Test and Tag 3 months N/A 3 months 12 months 3 months
7. Repaired, serviced and second-hand equipment After repair or service which could affect electrical safety, or on reintroduction to service